Heating system with energy-independent mode using multiple-layer streams of water
Abstract
A heating system for two, three and four floors of a building, involving the connection of a heated floor, with an energy-independent mode using multiple-layer streams of water, for achieving circulation, relating to the field of using thermal energy for heating buildings, using a single boiler. By designing the heating system, it is possible to obtain energy which is in addition to the boiler output, said energy carrying out circulation in the heating system and helping to make possible the feeding of heat carrier liquid, simultaneously: to the first floor, second floor and third floor; basement heating and heated floor circulation are achieved using a reversed flow, which involves: hotter water flowing into the boiler, thus decreasing heating outlays and, as a result, increasing efficiency. The pipes can be installed within walls and floors. Many options are taken into consideration for connecting a heated floor. The present invention is characterized in utilizing the opportunities of “multiple-layer streams of water” and in the entire process, i.e., supply and return, taking place within a single pipe, thus reducing materials costs by half. Within the heating system, the circulating volume of water is changed automatically.
Claims
exact text as granted — not AI-modified1 . The heating system for two, three and four floors, involving the connection of the heated floor, with an energy-independent mode using multi-layered streams of water to achieve circulation consisting of: the boiler, which is installed on the first floor and/or in the basement and/or two boilers on the same floor, connected through the supply riser 28 , where the unit 25 UNK-1-40, UNK-1-50 is tied-in into, with the supply manifold 11 —located: above the floor or concealed in the floor of the second floor, further the supply manifold 11 is loopback connected with the riser 13 , with the return manifold 12 —such independent loopbacks with their own manifolds can amount, at least, to two and more, but they shall be balanced in the physical resistance—achieved through the reduction of the manifold pipe diameters as compared to the supply riser 28 : the diameter of the supply manifold 11 and return manifold 12 depends on the level of load with the physical resistance of this loopback; the extension tank; the circulation pump in the basement 24 ; risers and heating instruments: on the first floor the radiator 2 is tied-in through the ball valves into the outermost riser 13 without in series connections with the riser, which loopback connects the supply manifold 11 with the return manifold 12 , the radiators 3 are connected through the ball valves to the risers 14 without in series connections with the riser, which also loopback connect the supply manifold 11 with the return manifold 12 , the radiator 4 , located near the boiler, is connected through the ball valves in series with the riser 15 so that they generate the resistance to the flow, in physical resistance and additionally, in order to generate resistance: we make the diameter of the risers 14 and 15 less as compared to the outermost riser 13 with the purpose to increase the delivery pressure, that allows the hot flow to reach the terminal radiator 2 , as the radiators 1 and 5 on the second floor and radiators 6 , 7 and 8 on the third floor are located higher than the supply manifold 11 , and as in the manifolds and in pipes, in general, there two main streams that appear: the hot layer, which is constantly aiming upwards and the colder layer, which flows down, if possible—we use the possibilities of the water multi-layer streams flow, two main streams appear in the manifolds, according to the laws of the heating engineering, we have the supply and return, due to the physical process the circulation is effected on the second and third floors: the radiators 1 on the second floor are tied-in through the ball valves mainly from above: the supply and return pipe of the radiator to the supply manifold 11 , the radiators 5 on the second floor, provided they are located to the side of the supply manifold 11 , are connected from one side to the radiator through the ball valves: the supply pipe of the radiator 17 , from the return pipe 18 and we tie-in mainly from above in 5-10 cm, this means close, into the supply manifold 11 , further we tie-in into the supply manifold 11 the pipes 19 and run to the third floor without in series connections, with the same diameter, they are mounted above the floor or concealed into the floor of the third floor and further come down and
are tied-in into the same supply manifold 11 , located on the second floor with the pipe 20 , depending on the building planning, it is possible to tie-in at the distance of 5-10 cm from each other or more—this means the supply pipe 19 from the return pipe 20 , and such separate independent loopbacks on the third floor can amount to 1 or 4 , where the radiators 6 , 7 and 8 are tied-in, the radiators 6 and 8 , located on the third floor, are installed similarly to connection of the radiators 1 , and the radiator 7 is installed similarly to the connection of the radiator 5 ,
as the water in pipes flows in layers—the colder water as compared to the hotter water has the higher specific gravity—through the riser 13 , 14 and 15 , which feed the radiators 2 , 3 and 4 , the cold streams are moved to the boiler from the radiators 1 and 5 of the second floor and from the radiators 6 , 7 and 8 of the third floor—thus, the circulation is increased, which increases an inflow of the hot water from the boiler to the supply manifold 11 ; at the same time we tie-in the risers 26 , 27 into the return manifold, run down into the basement or semi-basement, loopback connect with the terminal risers in the basement 26 : the return manifold 12 with the basement manifold 23 , to which we connect the radiators 9 through the ball valves, without in series connections—in the same way as we connected the radiators 2 and 3 , and to the risers 27 , which are near the boiler, we connect in series with the riser the radiators 10 through the ball valves, similarly to the connection of the radiators 4 , the diameter of the risers 26 and 27 is similar to that of the risers 14 and 15 on the first floor, we design as follows—the closer the radiator to the boiler, the higher physical resistance shall be generated, to build up the delivery pressure, further we tie-in the circulation pump 24 into the basement manifold and the supply of the circulation pump is tied-in into the supply riser 28 —higher than the unit 25 UNK-1-40, UNK-1-50—to move the used water from the basement manifold 23 to the supply manifolds 11 : the colder water gets into the lower layer of the supply manifold 11 and through the risers 13 , 14 and 15 , further through the return manifold 12 , gets into the main boiler, installed on the first floor 22 , or parallel to the main boiler 22 on the first floor, we install the electrical boiler 29 and tie-in as follows: the boiler return to the return manifold 12 , the boiler supply is tied-in above the unit 25 UNK-1-40, UNK-1-50 into the supply riser 28 , or we leave the electrical boiler 29 in its original place, i.e. on the first floor, and put the main boiler 22 and the unit 25 UNK-1-40, UNK-1-50 one floor lower, i.e. to the basement—to the place of the circulation pump 24 , we remove the pump, connect the return of the main boiler 22 with the basement manifold 23 —to the place, where the pump 24 was tied-in—the supply pipe from the main boiler 22 through the unit 25 is tied-in into the supply riser 28 on the first floor, higher than the electrical boiler 29 , and as we have in result two independent heating systems, it does not matter where the main boiler 22 is installed: the upper part of the building with three floors and independent basement operation—thus, we have large possibilities for various heating system operation modes: if we switch off the circulation pump in the basement 24 in order to save fuel,
and the main boiler 22 and unit 25 will stay switched on—in the option considered, provided the boilers are installed on the first floor and/or only one electrical boiler 29 is switched on, the heating system will operate in the entire building and in the basement as well, but in the basement more slowly, only water flow with the switched off circulation pump 24 in the basement will be effected vice versa: from the tie-in of the supply riser 28 , through the circulation pump 24 , to the basement manifold 23 and further through the radiator 9 and 10 to the return manifold 12 , and further to the main boiler 22 and/or to the electrical boiler 29 , and if we switch on the circulation pump 24 and switch off the unit 25 , the main boiler 22 will operate in the energy-independent mode—circulation in the building will be effected due to the water physical process and in the forced manner in the basement, and additionally the pump 24 will contribute to the circulation in the entire building, the only condition is that the pump in the basement 24 shall not be of too high capacity or we use the main boiler 22 in the daytime, and at night, we can switch on the electrical boiler 29 , or switch the heating system to the stand-by mode, when the owners are out and to switch off the main boiler 22 , unit 25 and circulation pump 24 , while the electrical boiler 29 will be switched on, the main work of the boiler will be for the three upper floors, and if the main boiler 22 is installed in the basement—the boiler is more loaded for the whole building with four floors, or we will switch off the main boiler 22 installed in the basement and the unit 25 and switch on the electrical boiler 29 on the first floor, then the water flow in the basement will be effected vice versa: from the tie-in of the supply riser 28 through the unit 25 to the main boiler 22 , further to the basement manifold 23 , through the radiators 9 and 10 to the return manifold 12 and to the electrical boiler 29 ; when connecting the heated floor, we can use the energy-independent mode for the heated floor circulation: parallel to the return manifold 12 and/or the basement manifold 23 , where we want to make the heated floor the pipes 30 are laid—straight, with small slope to let the air out—both ends are tied-in into the return manifold on the first floor 12 and/or into the basement manifold 23 , or in order to increase the delivery pressure on the heated floor, we use the used water from the third floor: we tie-in the return pipe from the third floor 20 , not as previously,—into the same supply manifold 11 , but we run down the return riser 20 from the third floor and connect to the header 31 installed on the first floor and/or connect to the header 31 in the basement, and we connect the header return to the return manifold 12 on the first floor and/or to the basement manifold 23 , we lay the header 31 straight, with slight slope in order to let the air out, in the direction opposite to the heat carrier flow or run down from the third floor the return pipe 20 and tie-in into the return manifold 12 on the first floor and/or tie-in one floor lower into the basement manifold 23 , into the pipe coming down from the third floor 20 we tie-in without in series connection:
the supply and return of the heated floor unit 32 , which operates in its closed loop circuit in the forced manner on the first floor and/or in the basement, as all buildings differ in terms of design, we can
connect the heated floor in the other way: we tie-in into the return manifold 12 , which is located horizontally on the first floor, the heated floor unit 31 , which operates forced in its closed loop circuit, we tie-in without in series connections, where we find it convenient—the supply line of the unit is tied-in at the distance of, at least, 15-20 cm or similar, to the return line—and we tie-in into the basement manifold 23 , located in the basement, the heated floor unit 34 , with such connection we shall mandatory connect two heated floor units for balancing and/or connect one heated floor unit—but it is tied-in in the same way into the return collecting manifold 35 , which connects the boiler with the return manifolds, and what is important is that the water stream leaving the unit 34 , as the heated floor operates with the circulation pump, the water stream enters the return manifold 12 and/or the basement manifold 23 and involves the mass of water from the whole heating system, thus increasing the circulation in the entire building, and for this purpose, we shall supply the water stream from the heated floor unit 34 to the return manifold 12 or the basement manifold 23 —in a guided way, to tie-in the return of the unit 34 into the return manifold 12 and/or the basement manifold 23 with the 45° angle; we use the physical process of water, where in the same pipe there are a lot of layers with various specific gravity flow—it is important to realize what the physical resistance is: the radiator 2 and 3 are tied-in into the risers, which loopback connect the supply manifold 11 with the return manifold 12 , without connections in series with the riser: the hottest water coming from above, will flow through the radiator and the colder water will flow along the riser into the boiler—the resistance will be low, this will increase the circulation or we tie-in the radiator 8 in series with the riser 15 , as the radiator contains the large amount of water and through constant heat emission, the heat carrier in the radiator cools down and the layers in the radiator are constantly changing: the hotter water fills the top part of the radiator and some pressure shall be applied to push the colder water from the radiator into the boiler, and this generates high resistance for the circulation, or we tie-in the radiator diagonally into the riser or the radiator return into the return manifold diagonally—this will cause several-fold higher physical resistance as many layers flow in the manifold—cold streams may partially or completely press the circulations.
2 . The heating system under the Cl. 1 differs through the fact that the supply riser 28 coming from the main boiler 22 is additionally equipped with the unit UNK-1-40, UNK-1-50, which can provide both forced circulation and the energy-independent mode—automatically.Join the waitlist — get patent alerts
Track US2017045235A1 — get alerts on status changes and closely related new filings.
We store only your email — no account needed. See our privacy policy.